現(xiàn)在 我們來(lái)演示三相交流風(fēng)機(jī)的接線方式,三相交流電機(jī)是一種比較常見(jiàn)的電機(jī),有星形和三角形兩種接法,以R4D310系列其中一款產(chǎn)品為例,黃綠線接地線PE,黑線接三相電源L1藍(lán)線接三相電源L2,棕線接三相電源L3,星形接法需要將黃線綠線白線短接在一起。
Now let’s show you. The three-phase AC motor is a relatively common motor, with two connection methods: star and delta. Take one of the R4D310 series products as an example. The yellow and green wires are connected to ground wires PE,
the black wire is connected to the three-phase power supply L1,
the blue wire is connected to the three-phase power supply L2,
the brown wire is connected to the three-phase power supply L3,
the star connection method requires the yellow, green and white wire to be short-circuited together.
三角形接法,需要分別將黑線和黃線短接,
藍(lán)線和綠線短接,棕線和白線短接,
注意有些風(fēng)機(jī)400V電壓下不能使用三角形接法以免造成風(fēng)機(jī)的燒毀,具體接線和供電方式可參考規(guī)格書(shū)。
兩根灰線是熱保護(hù)器,top輸出為常閉觸點(diǎn),當(dāng)繞組溫度高于top的設(shè)定值觸點(diǎn)就會(huì)斷開(kāi),
當(dāng)繞組溫度低于top設(shè)定值觸點(diǎn)就會(huì)閉合,
可以用在風(fēng)機(jī)的控制回路,以在繞組溫度高的時(shí)候切斷供電保護(hù)風(fēng)機(jī)。
For delta connection, you need to short-circuit the black wire and the yellow wire,
the blue wire and the green wire, and the brown wire and the white wire.
Note that some fans cannot use the triangle connection method under 400V voltage to avoid burning the fan. Please refer to the specification sheet for specific wiring and power supply methods.
The two gray wires are thermal protectors. The top output is a normally closed contact. When the winding temperature is higher than the top set value, the contact will open.
When the winding temperature is lower than the top set value, the contact will close.
It is used in the control loop of the fan to cut off the power supply to protect the fan when the winding temperature is high.